2.5        Fire Detection and Fire Alarm Systems

2.5.1            Existing Fire Detection and Alarm System

The primary fire alarm systems serving BWI Marshall is the Honeywell EBI (Enterprise Building Integration) System).

 

The signals report to a Honeywell EBI Graphics System located in the BWI Marshall Dispatch Center (BWI Marshall Dispatch).

 

The fire alarm components in the terminal building shall be as follows:

A.     Fire Alarm Notification Appliances

1.      Notification Signals:

a.      Terminal Building - all areas will be zoned as either a public area or a tenant area.

b.      Public areas shall have visual appliances (strobe lights) and audible appliances (horns). Emergency announcements shall come from terminal-wide public address (PA) system. In the event of a failure of the PA System, horns will be activated manually from the BWI Marshall Dispatch. All appliances in this zone, horns and strobes, shall be activated separately via manual control from the BWI Marshall Dispatch. Horns shall be silenced during PA System announcements without silencing the strobes. Upon completion of announcements, the horns shall reactivate.

c.      Tenant areas shall have audio/visual (horn/strobe) notification. Publicly accessible portions of tenant spaces shall have PA speakers for emergency announcements as noted above. All appliances in this zone shall be automatically activated by the associated FS-90 FACP or the XLS panels.

2.      Remote Annunciators shall not be provided unless otherwise required by the Office of the Fire Marshal.

3.      EBI Central Color Graphic Computers shall be programmed and updated as required by expansions and modifications to the Fire Alarm. System. Cost of programming and computer upgrades shall be included in the construction project along with associated construction costs.

B.     Fire Alarm Initiating Devices

Addressable Interface Units (monitoring modules) shall be used to monitor indicating devices that are not otherwise equipped for multiplexed addressable communication such as sprinkler valve tamper switches.

1.      Manual Pull stations shall be addressable double action type without glass rod inserts. Provide waterproof Lexan covers on pull stations located outdoors and in parking garages.

2.      All surface mounted smoke detectors shall be addressable photoelectric type. Ionization type detectors are not permitted.

3.      Duct Smoke Detectors shall be addressable photoelectric type.

4.      Heat Detectors shall be addressable combination rate of rise and fixed temperature type within air-conditioned spaces.

5.      Pressure Switches for pre-action systems, shall be supplied with addressable monitoring modules.

6.      Water Flow Switches for sprinkler systems, shall be supplied with addressable monitoring modules for alarm conditions.

7.      Fire Extinguishing System Control Panels for fire suppression systems (such as carbon dioxide systems, clean agent, foam systems, etc.) shall be supplied with addressable monitoring modules.

C.      Fire Alarm Supervisory / Control Devices

Special provisions for exhausting noxious or hazardous atmospheres shall be designed on a per project basis. The design shall utilize HVAC systems and controls; zoning strategies and supplemental exhaust.

 

2.5.2            New Fire Detection and Alarm System

A.     The Office of the Fire Marshal is the local Authority Having Jurisdiction for MDOT MAA owned facilities. The Consultants must coordinate with the Office of the Fire Marshal during the design of fire detection and alarm systems. Submit relevant drawings and specifications to MDOT MAA FDE for transmittal to the Office of the Fire Marshal for review at each required submission. At a minimum MDOT MAA recommends meeting with the Office of the Fire Marshal prior to 50% completion of design. General requirements of the Office of the Fire Marshal include, but are not limited to, the following:

B.     The Fire Detection and Alarm System shall comply with the following requirements:

1.      Conductors and Circuit Type:

a.      Initiating circuits shall be Class A

b.      Indicating circuits shall be Class A

c.      Only copper conductors shall be used. Conductor wire shall be solid. Stranded conductors will not be allowed. The only exception allowed for stranded wire will be for the installation of speakers in a fire alarm controlled voice evacuation system.

2.      Conductor Size:

a.      Initiating circuits shall be a minimum of No. 14 AWG twisted pair. No. 16 AWG may be used, if pre-approved by the Office of the Fire Marshal, for initiating circuits, depending on electrical system design and manufacturer's requirements. No. 18 AWG shall not be permitted.

b.      Indicating circuits shall be a minimum of No. 12 AWG.

3.      Conductor Requirements:

a.      Insulation - THHN or THHW (NEC Article 310, Table 31016).

b.      Voltage Rating· 600 volt.

c.      Temperature Rating· 90°Cl194°FP.

d.      No. 14 AWG shall have 6 turns per foot.

e.      No. 16 AWG shall have 10 turns per foot.

4.      Color Codes:

a.      Work on new systems shall comply with equipment manufacturer's requirements.

5.      Work on existing systems shall match existing color-coding of wire in Volume 2, Chapter 11 Electrical. Conduit:

a.      All fire alarm wiring shall be in conduit complying with applicable NEC articles. (Exception: Existing speaker wiring which serves as part of the PA portion of the fire alarm system may remain as presently installed, without conduit, unless an area is renovated to an extent that the Office of the Fire Marshal determines that encasement in conduit is required.)

6.      Identification of conduit and junction boxes will be done with red paint and wording that clearly identifies the installation as being a fire alarm system. Panel Connections:

a.      Shall be on the left hand or right hand sides. No connections shall be done from the bottom.

b.      Top mount connections shall be permitted only if waterproof connectors are used.

7.      Power Supply:

a.      All fire alarm systems shall be provided with a primary and a secondary power supply.

b.      Secondary power shall automatically supply the energy to the system within 30 seconds. Secondary power shall be from a storage battery capable of operating the complete alarm system in normal or supervisory (non-alarm) mode for a period of 24 hours and at the end of this period, have sufficient capacity to operate the system, including alarm indicating devices in either alarm or supervisory mode for a period of 15 minutes. This requirement applies to new panel installations and any existing panels affected by renovation work.

c.      The batteries in all Fire Alarm Control Panels (FACPs) shall be supervised.

d.      An engine-driven generator with automatic transfer switch arranged in accordance with NFPA 72 may be used for secondary power in lieu of storage batteries.

8.      Fire Alarm Control Panel Location:

a.      Shall be determined by the Office of the Fire Marshal only.

b.      Shop drawings shall include a floor plan showing the location of the fire alarm panel.

c.      Fire alarm system zones shall follow fire protection sprinkler zones as appropriate.

C.      All duct type smoke detectors shall be provided with remote test switches and indicator lights with identification signage. The test switches shall be readily accessible and have readily visible (below ceiling) indicators. Smoke detectors shall be provided with two sets of contacts. One set for alarm and one set to shut down related HVAC equipment. All duct detectors shall be accessible for inspection, maintenance, repair and replacement.

D.     All sprinkler water flow, switches and tamper switches shall be connected to the fire alarm system.

E.      The Honeywell EBI Graphical Central Computer shall be programmed with a specific designation of the alarm location (for example, boarding bridge gate number or other geographic locator).

F.      Install a dedicated MDOT MAA "IN-HOUSE" telephone adjacent to all fire alarm control panels (FACP). This requirement applies to new panel installations and any existing panels affected by renovation work. Design shall include an empty conduit between the proposed telephone location and the nearest telephone closet. Coordinate with MDOT MAA Telecom Section for MDOT MAA to install the telephone

G.     YOU ARE HERE" designation and the egress paths clearly shown on a floor plan. Permanent signage, with the capability for changing inserts, shall be specified to be included in the construction contract. See Chapter 2.3.1 Terminal Evacuation Plans. Provide a floor plan submittal showing the proposed locations of the evacuation plans(s) for approval by the Office of the Fire Marshal.

H.     Signs shall have red lettering and a white background encased or enclosed in an approved box. Provide directional exit signs in the main corridor of the concourses (piers) to direct occupants to the exit stairs along the exterior holdroom walls.

 

2.5.3            Fire Detection Systems Table

 

AUTOMATIC FIRE AND SMOKE DETECTION SYSTEMS REQUIRED

Areas Protected

Smoke Detection

Communication Rooms

X

Electrical Sub-Station Rooms

X

Tenant Space Transformer Rooms

X

Hazardous Materials Storage Rooms

X

Bag Belts at fire rated assemblies

X (Note 1)

Airfield Light Vaults

X

Automatic Smoke Doors at Pedestrian Tunnels

X (Note 2)

Automatic Smoke Doors at Skywalks

X (Note 2)

 

NOTES FOR TABLE “AUTOMATIC FIRE AND SMOKE DETECTION SYSTEMS REQUIRED”

1.      Smoke detectors are not required on both sides of fire rated assemblies where bag belt penetrations occur provided the fire shutters activate upon water flow alarm.

2.      Smoke detectors are required on both sides of smoke doors at Skywalks and Pedestrian Tunnels. They are to activate the smoke doors or fire doors at each opening.

3.      Wherever “Heat Detection” is required above, combination Rate-of-Rise and Fixed Temperature (ROR-FT) detectors may be used except where specifically “Heat Detection Only” is listed (e.g. – Break rooms with kitchenette, Elevator shunt trip, Kitchens). In “Heat Detection Only” locations, combination ROR-FT detectors may not be used, however it is permissible to install ROR-FT detectors in those locations if only the FT portion of the combination detector is wired to be functional for detection notification.

4.      Fire Alarm Control Panels (FACP) are not to be set to provide automatic building evacuation signaling in public areas upon receipt of a water flow, smoke, heat detection signal, or manual pull station activation, but are to provide automatic evacuation signaling in tenant areas. They are to transmit a fire alarm signal to the Emergency Communications Center (BWI Marshall Dispatch). All FACPs are to be non-self-resetting.

 

2.5.4            Manual Fire Alarm Pull Station Table

 

NFPA 72 MANUAL FIRE ALARM PULL STATIONS REQUIRED

Areas Protected

Manual Pull Station

Exit Doors and Egress Stairwells

X (Note 1)

Fire Doors at Skywalks

X (Note 2)

 

NOTES FOR TABLE “NFPA 72 MANUAL FIRE ALARM PULL STATIONS REQUIRED”

1.      Fire alarm pull stations are required at each main exit door, each egress stair, and at each vestibule leading to the outside. They are not required at tenant space public entrances/exits unless travel distance requires it.

2.      Fire alarm pull stations are required on the terminal side of skywalk doors and on the parking garage side of skywalk doors.

 

2.5.5            Martin State Airport (MTN)

MTN has various fire alarm system manufacturers (Honeywell, Tyco Integrated Security, Simplex, etc.). Contact the Office of the Fire Marshal in advance to coordinate any work involving replacement, modifications, or extensions to any existing fire alarm equipment.

 

2.5.6            Fire Alarm Communication Requirements

2.5.6.1          Panels Reporting to Central Station

Existing Plain Old Telephone Service (POTS) lines are permitted to remain in use until the fire alarm panel is replaced. All new and upgraded fire alarm panels shall report to central station via cellular or radio. Other means of communication may be presented to the Office of the Fire Marshal for approval. One form of communication is permitted if NFPA 72 requirements are followed. Otherwise, two forms of communication are required.

 

Existing fire alarm panels may continue to transmit zone information only to central station. All new and upgraded fire alarm panels shall report point addresses for the alarm, supervisory, and trouble signal(s) to central station. Submittal packages shall indicate how all required signals are being transmitted to central station. Product data for shared communications equipment shall be submitted for review prior to installation.

 

2.5.6.2          Panels on Networks

All new fire alarm control panels in MDOT MAA owned facilities on MDOT MAA property shall be connected to the existing network. If the existing network is not available, central station requirements above may be considered if approved by the Office of the Fire Marshal.